Rotronic CF8-W-Disp-CO User Manual

Browse online or download User Manual for Communication Rotronic CF8-W-Disp-CO. ROTRONIC CF8-W-Disp-CO User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Dokument
UMA 147
Rev
1
Page
1 (16)
User manual
CF8-W-Disp-CO
CO
2
/ CO sensor with built-in general purpose
controller
General
The IAQ-sensor product CF8-W-Disp-CO is used to measure indoor air carbon
dioxide and carbon monoxide concentrations. It is a very flexible controller with
programmable outputs for both relay- and linear control of e.g. mixed air dampers,
humidifier and fans. The measured values are shown on the display.
The unit can alternatively be connected to common VAV (Variable Air Volume)
controllers, or Direct Digital Control (DDC). The linear output functions are pre-
programmed. All functions can be modified from a PC with the software UIP (version
4.3 or higher) and the RS232 communication cable.
Figure 1 CF8-W-Disp-CO for wall mounting
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - CF8-W-Disp-CO

Dokument UMA 147 Rev 1 Page 1 (16) User manual CF8-W-Disp-CO CO2 / CO sensor with built-in general purpose controller General The IAQ-s

Page 2 - FUNCTIONAL DESCRIPTION

Dokument UMA 147 Rev 1 Page 10 (16) Figure 10 Maintenance functions available on CF8-W-Disp-CO to set output limits. Only flow chart for set

Page 3

Dokument UMA 147 Rev 1 Page 11 (16) 4. Push ENTR(+-) once. The display shows EC and two digits. Enter the access code to the service menu.

Page 4 - Output Configurations

Dokument UMA 147 Rev 1 Page 12 (16) setting and return to Set H. Push MENU(+) or ESC(-) to return to Set H without saving the new setting. Pu

Page 5

Dokument UMA 147 Rev 1 Page 13 (16) Test gas verification If the measurement of a sensor is to be verified, a test gas with carefully determi

Page 6 - Display modes

Dokument UMA 147 Rev 1 Page 14 (16) PLEASE NOTE! The sensor accuracy is defined at continuous operation (at least 3 weeks after installation)

Page 7 - Maintenance level

Dokument UMA 147 Rev 1 Page 15 (16) 6 64 Memory Error Non-fatal error during memory operations. Check detailed settings and configuration wi

Page 8

Dokument UMA 147 Rev 1 Page 16 (16) DI1~+ Figure 12. The CF8-W-Disp-CO printed circuit board with the connection terminal area is enlarged. T

Page 9

Dokument UMA 147 Rev 1 Page 2 (16) FUNCTIONAL DESCRIPTION CF8-W-Disp-CO is delivered pre-programmed (see description below). The user can a

Page 10

Dokument UMA 147 Rev 1 Page 3 (16) Standard configuration: Out(1) is carbon monoxide output, Out(2) is carbon dioxide output and Out(3) is re

Page 11

Dokument UMA 147 Rev 1 Page 4 (16) Output Configurations A label on the inner side of the sensor lid shows the configuration of the output

Page 12 - / CO sensor CF8-W-Disp

Dokument UMA 147 Rev 1 Page 5 (16) Jumper Position Function Start point selection jumper 0% 20% Jumper top position provides 0Vdc o

Page 13 - Test gas verification

Dokument UMA 147 Rev 1 Page 6 (16) Push Button Operation for CF8-W-Disp-CO This sensor has two push buttons, MENU and ESC. The YELLOW LED w

Page 14 - Error code and action plan

Dokument UMA 147 Rev 1 Page 7 (16) the set points of temperature and CO2 After power up the display will always return to the Default display

Page 15 - Maintenance

Dokument UMA 147 Rev 1 Page 8 (16) 6d1 The present MIN value in % of FS no Increase the MIN value by stepping with the MENU(+) button. Decrea

Page 16

Dokument UMA 147 Rev 1 Page 9 (16) EXAMPLE I: Setting of the MAX value of the analogue outputs The access code is time limited. If the time