Rotronic AG
Bassersdorf, Switzerland
HygroFlex HF5 Humidity Temperature
Transmitters: User Guide
© 2009-2013; Rotronic AG E-M-HF5-V1_25
User defined description
The device name of the HC2 probe is not displayed by HW4 and is
replaced with the HF5 Input Name
Psychrometric calculation
HF5 setting overrides HC2 probe setting
This setting has no effect on the HF5 and probe. Depending on the
model, the data refresh rate is as follows:
HF52: typically 5 s
HF53 and HF55: typically 1 s
Generates fixed humidity and / or temperature value
When enabled, the HF5 settings override the HC2 probe settings
The HF5 setting overrides HC2 probe setting regarding the HF5
signals. The HC2 probe settings still apply when the probe is used
alone
Make sure to use the same humidity symbol and the same
temperature unit for both the HF5 and probe.
Out-of-limits value alarm
The HF5 settings are independent from the HC2 probe settings.
The HC2 probe settings have an effect only when the HF5 is
enabled to monitor alarms generated by the probe
When out-of-limit values have been defined for the same parameter
for both the HF5 and probe, any alarm is triggered based on the
narrowest set of limits (assuming that the HF5 has been set to
monitor probe alarms).
Parameter and scale
The HC2 probe settings have no effect on the HF5